Chapter 9

From sky to substation: GICs

This is where space weather meets the power grid. A rapidly changing magnetic field pushes slow, steady currents through the ground and into long transmission lines. These geomagnetically induced currents (GICs) then flow through transformers, which aren't designed to carry them.

In this chapter

  • How a changing magnetic field creates an electric field in the ground
  • Why the rocks under our feet, and the way the grid is laid out, both matter
  • How GIC gets into the network through transformer neutrals
  • What GIC does to transformers, and to the wider power system
  • What's happened here in New Zealand, and how operators manage the risk

Step 1: a changing field makes a voltage

In 1831, Michael Faraday discovered that a changing magnetic field creates an electric field. It's how every power station generator works (spin a magnet past a coil of wire and electricity flows), and it's also how a wireless phone charger works (so there's a good chance you've got a wee demo of it on your bedside table).

During a geomagnetic storm, the whole of Earth's surface is sitting under a magnetic field that's changing quickly. That change creates an electric field in the ground itself, called the geoelectric field, and it's measured in volts per kilometre (V/km). On a quiet day it can be well under 0.1 V/km, and in a severe storm over poorly conducting rock it can reach several V/km.

Think of it like

The whole country turning into a very slow, very large generator. The "magnet" is the storm's currents 100 km overhead, and the "wire" is anything long and conducting on the ground (transmission lines being the big one in this chapter).

Step 2: the ground underneath matters

How big the geoelectric field gets depends a lot on what the ground is made of:

New Zealand's geology is complex, so two places under the same magnetic disturbance can end up with quite different geoelectric fields. That's one reason modelling GIC for New Zealand needs detailed maps of ground conductivity (how easily current flows through the ground).

Step 3: into the grid

High-voltage transmission transformers are usually connected to earth at their neutral point, for safety. That means a long transmission line, the transformers at each end and the earth between them all form one giant loop. The geoelectric field pushes current around that loop - along the line, down through one transformer's neutral, through the ground, and back up through the other one.

150 nT/min 0° GIC
How GIC flows. The geoelectric field (orange arrows) drives a slow, near-steady current around the loop made by the line, the two transformers and the earth. A higher rate of change means more current. Lines that line up with the electric field collect the most, and a line at right angles collects very little. The "GIC" number is just for illustration.

GIC is called quasi-DC (almost direct current) because it changes over seconds to minutes, which is very slow compared with the 50 cycles per second of the grid's alternating current. As far as the power system is concerned, it looks like a direct current added on top of the normal AC sine wave.

What makes GIC bigger at a particular place

Local rate of change

Faster change means a stronger geoelectric field, and more GIC.

Ground conductivity

Resistive ground gives you larger electric fields.

Electricity networks

The geoelectric field drives a voltage along each line, equal to the field added up along the line's route, so it's largest on long lines running in the same direction as the field. GIC then flows through the lines, the windings of earthed transformers and the substation earth mats, and how it splits between paths depends on the resistance of connected components.

Step 4: what GIC does to a transformer

A transformer works by sending an alternating magnetic flux back and forth through its iron core. The core is designed to work comfortably within a certain range. A steady DC current from GIC adds a constant "offset" to that flux and pushes it off-centre. Then, around the peak of one half of every AC cycle, the flux gets pushed past what the iron can handle, and the core saturates (the iron is maxed out, so pushing the flux any further takes a lot more current).

0 A
Half-cycle saturation. The top plot is the magnetic flux in the transformer core, and the bottom one is the current the transformer draws to magnetise its core. When the flux crosses into saturation, that current develops large, distorted spikes. The values are just for illustration, as real thresholds depend on the transformer's design.

Those spikes set off a chain of problems:

EffectWhat happensWhy it matters
HeatingStray magnetic flux escapes the saturated core into the tank and metal parts, causing hot spots.Ages insulation and can permanently damage a transformer if it lasts long enough.
Reactive power demandSaturated transformers draw much more reactive power (VArs).Voltages sag across the network and are harder to control. In the worst case this can contribute to voltage collapse.
HarmonicsThe spiky current is full of harmonics: multiples of 50 Hz.Protection relays and equipment such as capacitor banks and static VAr compensators (SVCs) can mistakenly trip, removing support just when it's needed.
Noise and vibrationTransformers hum loudly and vibrate.A visible (audible) sign of saturation.
The 1989 lesson

On 13 March 1989, a severe storm caused harmonics that tripped several static VAr compensators on Hydro-Québec's network in Canada. Within about 90 seconds the system had collapsed, leaving around six million people without power for about nine hours. Nothing "burned out" first - the problem was the system losing its voltage support.

New Zealand's experience

New Zealand found out about GIC first-hand in November 2001. A large storm set off widespread transformer neutral current alarms in the South Island, tripped equipment at Islington substation near Christchurch, and damaged a transformer at Halfway Bush substation in Dunedin beyond repair.

Since then:

Why New Zealand?

New Zealand is long and skinny, with long transmission lines, a mid-to-high geomagnetic latitude in the south, complex geology and plenty of coastline. Put all that together and GIC is a real consideration here, even though we're a long way from the poles.

Other long conductors

GIC isn't just a power-grid problem. It can also affect pipelines (by interfering with their corrosion protection), railway signalling, and long communication cables, including the power-feed systems of undersea cables.

Key takeaways

  • A rapidly changing magnetic field creates a geoelectric field in the ground (that's Faraday's law at work).
  • That field drives slow, near-DC GIC around the loops made by lines, earthed transformer neutrals and the ground.
  • How big GIC gets depends on the local rate of change, ground conductivity, line length and direction, and network layout.
  • In transformers, GIC causes half-cycle saturation, which brings heating, extra reactive power demand and harmonics.
  • New Zealand has first-hand experience (2001, 2024), measures GIC in real time, and has operational plans to reduce it.

Check your understanding

1. What pushes GIC into the power network?

The particles never make it down to the ground. The changing field induces a geoelectric field, and that pushes current through long conductors that are earthed at both ends.

2. Why can just a few tens of amps of DC cause trouble for a large transformer?

Transformer cores are designed for AC, and a DC offset pushes them into saturation on one half of every cycle.

3. Two lines are the same length and in the same storm. One runs along the direction of the geoelectric field, and the other runs at right angles to it. Which one carries more GIC?

The voltage driving GIC depends on the part of the electric field that lies along the line. The field's direction changes during a storm, though, so different lines can be the most affected at different times.